If these are all two wire circuits hot and neutral the number of current carrying conductors in the emt is 12 and these wires must be derated to 50 percent of their ampacity shown in table 310 16.

Derating wires in a gutter.

The rate at which heat is dissipated to the environment depends on many factors but the two main requirements in the nec for derating ampacity are ambient. Derating conductors for the environment where they are installed is an important consideration for selecting the type and size of conductor for a particular installation. Derating factors depending on the installation environment of the cable ampacity ratings may need to be adjusted or derated to control heat flow. When installing a system on a rooftop special consideration must be given to the ambient temperature inside the wire way or conduit that contain the conductors to prevent heating beyond the rating of the insulation of the.

Each current carrying conductor of a paralleled set of conductors shall be counted as a current carrying conductor. Adjustment factors for conductors in sheet metal auxiliary gutters are in 366 23 a and adjustment factors for conductors in metal wireways are in 376 22 b. Seems like a big jump from 0 to 40 derating going from 30 to 31 ccc. Therefore if a conduit has four wires in it and one of those wires is a ground wire the conductors do not require derating since only three carry current.

There are two important rules to remember when installing metal wireways. In auxiliary gutters and metal wireways it is not required to derate the ampacity of conductors if the number of current carrying conductors is 30 or less. Ground wires are not considered current carrying conductors. According to the 2014 nec.

At any cross section cable derating may be required see nec 362 5 note. In other words if you had a wireway with 31 ccc in the cross section for 1 derating is required. Wireway and wiring trough frequently asked questions 25701 science park drive cleveland ohio 44122 216 464 3400. And according to 240 4 they must be protected by a 15a fuse or circuit breaker.

The adjusted ampacity for each conductor is 30 x 0 5 15. Derating applies to current carrying conductors only. Conductors cannot fill more than 20 of the interior cross sectional area of a wireway per 376 22 a.

Definition 376 22 Mike Holt S Forum